Siemens Relays

This article provides the relays for two Siemens lighting systems, the N372 and N350.

Written by Brian Matheron

Updated at April 17th, 2025

Table of Contents

Siemens N372 Siemens N350

Siemens N372

Group Address Timeclock 2000A1 Timeclock 2000A2 & B2 Timeclock 2000C1 & C2 Timeclock 2000D Config ID
1/0/1 Time Channel 1: Signs n/a n/a n/a 1
1/0/2 Time Channel 2: Parking n/a n/a n/a 2
1/0/3 Time Channel 3: Sales Normal n/a n/a n/a 3
1/0/4 Time Channel 4: Sales Maintenance n/a n/a n/a 4
1/1/0 Security: Disarm n/a n/a n/a 5
1/1/1 Security: Burglar Alarm Override: Parking n/a n/a 6
1/1/2 n/a Override: Signs n/a n/a 7
1/1/3 n/a Override: Sales n/a n/a 8
1/1/4 n/a Override: Future n/a n/a 9
1/1/5 n/a Wisconsin Override: Interior Odd n/a n/a 10
1/1/6 n/a Wisconsin Override: Interior Even n/a n/a 11
1/1/7 n/a Wisconsin Override: Photo n/a n/a 12
1/1/8 n/a Override: Future II n/a n/a 13
1/2/0 Override: Parking n/a n/a n/a 14
1/2/1 Override: Signs Security: Disarm n/a n/a 15
1/2/2 Override: Sales Security: Burglar Alarm n/a n/a 16
1/2/3 Override: Future Security: Burglar Alarm II n/a n/a 17
1/3/0 Honeywell Controller: 20 Footcandles (Stg 1) n/a n/a n/a 18
1/3/1 Honeywell Controller: 100 Footcandles (Stg 2) Honeywell Controller: 20 Footcandles (Stg 1) n/a n/a 19
1/3/2 n/a Honeywell Controller: 100 Footcandles (Stg 2) n/a n/a 20
1/4/0 Logic: Time A & 100 Footcandles n/a n/a n/a 21
1/4/1 Logic: Time B & 20 Footcandles Time Channel 1: Signs n/a n/a 22
1/4/2 n/a Time Channel 2: Parking (No Time) n/a n/a 23
1/4/3 n/a Time Channel 3: Sales Normal n/a n/a 24
1/4/4 n/a Time Channel 4: Sales Maintenance n/a n/a 25
1/4/5 n/a Time Channel 5: Sales Normal II n/a n/a 26
1/5/0 Timer 1A n/a n/a n/a 27
1/5/1 Timer 1B: Off 15 Minutes after Arm Logic: Time A & 100 Footcandles n/a n/a 28
1/5/2 Timer 1C: Disarm Logic: Time B & 20 Footcandles n/a n/a 29
1/5/3 Timer 1D n/a n/a n/a 30
1/6/2 n/a Timer 1A: Arm Delay n/a n/a 31
1/6/3 n/a Timer 1B: Timeswitch Parking n/a n/a 32
1/6/4 n/a Timer 1C: Timeswitch Exterior Signs n/a n/a 33
1/6/5 n/a Timer 1D: Timeswitch Interior All n/a n/a 34
1/6/6 n/a Timer 2B: Timeswitch Interior Odd n/a n/a 35
1/6/7 n/a Timer 2C: Timeswitch Interior Even n/a n/a 36
1/6/8 n/a Timer 2D: Timeswitch Photo 17 n/a n/a 37
1/6/9 n/a Timer 2A: Future n/a n/a 38
1/6/10 n/a Timer 1D: Timeswitch Interior All II n/a n/a 39
1/6/11 n/a Timer 2B: Timeswitch Interior Odd II n/a n/a 40
2/1/1 n/a n/a Override: Parking Override: Parking 41
2/1/2 n/a n/a Override: Signs Override: Signs 42
2/1/3 n/a n/a Override: Sales Override: Sales 43
2/1/4 n/a n/a Override: Future Override: Future 44
2/1/5 n/a n/a Wisconsin Override: Interior Odd Wisconsin Override: Interior Odd 45
2/1/6 n/a n/a Wisconsin Override: Interior Even Wisconsin Override: Interior Even 46
2/1/7 n/a n/a Wisconsin Override: Photo Wisconsin Override: Photo 47
2/1/8 n/a n/a Override: Future II Override: Future II 48
2/2/1 n/a n/a Security: Disarm Security: Disarm 49
2/2/2 n/a n/a Security: Burglar Alarm Security: Burglar Alarm 50
2/3/1 n/a n/a Honeywell Controller: 20 Footcandles (Stg 1) Honeywell Controller: 20 Footcandles (Stg 1) 51
2/3/2 n/a n/a Honeywell Controller: 100 Footcandles (Stg 2) Honeywell Controller: 100 Footcandles (Stg 2) 52
2/4/1 n/a n/a Time Channel 1: Signs Time Channel 1: Signs 53
2/4/2 n/a n/a Time Channel 2: Drive Thru Time Channel 2: Parking 54
2/4/3 n/a n/a Time Channel 3: Sales Time Channel 3: Sales Normal 55
2/4/4 n/a n/a Time Channel 4: Pharmacy Time Channel 4: Sales Maintenance 56
2/5/1 n/a n/a Logic: Time 1 & 100 Footcandles: Signs Logic: Time 1 & 100 Footcandles: Signs 57
2/5/2 n/a n/a Logic: Time 2 & 100 Footcandles: Drive Thru n/a 58
2/5/3 n/a n/a Logic: Time 1 & 20 Footcandles: Parking Logic: Time 1 & 20 Footcandles: Parking 59
2/5/10 n/a n/a Flashing n/a 60
2/6/1 n/a n/a Status: Parking Status: Parking 61
2/6/2 n/a n/a Status: Signs Status: Signs 62
2/6/3 n/a n/a Status: Interior Odd Status: Interior Odd 63
2/6/4 n/a n/a Status: Interior Even Status: Interior Even 64
2/6/5 n/a n/a Status: Photo Status: Photo 65
2/6/6 n/a n/a Status: Future Status: Future 66

 

Siemens N350

Group Address Timeclock 2000A1 Config ID
4/0/1 Security Disarmed 1
4/0/2 Security Burglar Alarm 2
4/0/3 TVSS Failure 3
4/0/4 Future Input 4
4/6/1 OVR Sales 5
4/6/2 OVR Pharmacy 6
4/6/3 OVR Signs 7
4/6/4 OVR Parking 8
4/6/5 Pharmacy OVR Inside 9
4/6/6 Pharmacy OVR Drive Thru 10
4/6/7 OVR Liquor 11
4/7/3 Below 20 Foot Candles (200 LUX) 12
4/7/4 Below 100 Foot Candles (1000 LUX) 13
4/7/5 Below 50 Degrees (10C) 14
4/7/6 Below 32 Degrees (0C) 15
4/7/7 Below 25 Degrees (-4C) 16
4/0/5 Schedule 24 Hour 17
4/0/6 Schedule Store -30 Minutes 18
4/0/7 Scheudle Pharmacy -5 Minutes 19
4/0/8 Schedule Liquor -5 Minutes 20
4/0/9 Schedule Clinic -5 Minutes 21
4/0/10 Schedule Group 8 22
4/0/11 Schedule Groups 2, 2A, 11 23
4/0/12 Schedule Group 3 24
4/0/13 Schedule Groups 7, 12, 16, 19 25
4/0/14 Schedule Group 9 26
4/0/15 Schedule Group 5 27
4/0/16 Schedule Group 10 28
4/0/17 Schedule Group 15 29
4/0/18 Schedule Group 18 30
4/0/19 Future 31
4/0/20 Future 32
4/0/21 Future 33
4/0/22 Future 34
4/5/1 Group 1: Sales Maintenance 35
4/5/2 Group 2: Sales Normal 36
4/5/3 Group 3: Sales Evening 37
4/5/4 Group 4: Wall Heaters 38
4/5/5 Group 4A: Entrance Heater w Vest 39
4/5/6 Group 4B: Entrance Heater wo Vest 40
4/5/7 Group 5: Pharmacy 1 41
4/5/8 Group 5A: Pharmacy 2 42
4/5/9 Group 6: Wall Packs 43
4/5/10 Group 7: Exterior Signs 44
4/5/11 Group 7A: Awning Canopy 45
4/5/12 Group 8: Employee Parking 46
4/5/13 Group 9: Customer Parking 47
4/5/14 Group 10: Drive Thru Canopy 48
4/5/15 Group 11: Gondala Recpts 49
4/5/16 Group 12: Façade Accents 50
4/5/17 Group 13: LED Readerboard 51
4/5/18 Group 14: Security Canopy 52
4/5/19 Group 15: Liquor Dept 53
4/5/20 Group 16: Interior Signs 54
4/5/21 Group 17: Interior Night Lights 55
4/5/22 Group 18: Clinic 56
4/5/23 Group 19: Sales Floor by Windows 57
4/5/24 Group 20: Sales Perimeter 58

Did you find this article helpful?

Yes
No

More Information

  • Equipment - Lighting Siemens - Device Offline
  • Equipment - Lights Siemens - Lights Not Following Schedule
  • Equipment - Lighting Siemens - Lights Partially Faulting

See More On

siemens switches
Privacy Policy | Terms & Conditions

©2025 All Rights Reserved

Expand